Suryamon: health monitoring for solar power plants
From inverter to dashboard in one Docker command: Modbus telemetry, IEC 61724-1 indicators and string anomaly alerts.
| Suryamon | |
|---|---|
| Class | Solar plant monitoring stack |
| Language | Python |
| Protocol | Modbus TCP, SunSpec models 1, 103 and 160 |
| Standard | IEC 61724-1 |
| Licence | Apache 2.0 |
| Repository published | July 2026 |
| Source | GitHub |
Inverters report power, temperature and energy every few seconds, but many operators of small and mid-size plants never see the data. Dust on one section, a blown fuse or an overheating inverter can reduce output for months unnoticed. Suryamon reads the data, computes health indicators and raises an alert that names the likely physical cause.
Architecture
Six small services run under Docker Compose.
- Inverters Modbus / SunSpec
- Collector Polls every 10 seconds
- VictoriaMetrics Time-series storage
- Analytics and alerts Indicators every 5 minutes; rules every 60 seconds
- Operator Grafana, email, Slack or webhook
Design decisions
| Decision | Reason |
|---|---|
| Prometheus metric model | Telemetry is time-series data, so storage, queries and dashboards are inherited |
| Collector holds no state | It can be restarted at any time |
| Analytics runs as a batch loop | The indicators are periodic totals |
| Performance Ratio only with irradiance data | The system never invents a figure it cannot compute |
| Simulator included | Every feature can be shown without hardware |
Indicators
| Indicator | Meaning |
|---|---|
| Performance Ratio | Share of the available solar energy that was captured |
| Capacity utilisation factor | Energy delivered against continuous full-power output |
| Specific yield | Energy per kilowatt-peak installed |
| String anomaly score | How far each panel string departs from its peers |
Built-in alerts
| Alert | Fires when | Likely cause |
|---|---|---|
| Inverter offline | No successful poll for 5 minutes | Network down or inverter off |
| String underperforming | Anomaly score above 0.15 for 30 minutes | Soiling, shading or connector fault |
| String dead | Score above 0.90 for 15 minutes | Blown fuse, connector or isolation fault |
| Performance degraded | Daily ratio below 0.75 for 2 hours | Soiling, curtailment or clipping |
| Soiling drift | 3-day average 5% below the 3-week baseline | Dust accumulation |
| Over temperature | Cabinet above 65 °C for 10 minutes | Blocked ventilation or failed fan |
Testing
Indicator calculations are checked against IEC 61724-1 reference cases. The simulator and collector exchange data over real TCP in the tests, every alert and dashboard query is parsed, and a second stage runs the whole Docker stack.
Roadmap
Planned: Modbus RTU, MQTT ingest, satellite irradiance, better inverter views, a multi-plant view and an open-hardware data logger.